banner
Home / Products / Energy Meter
Products
Amc72L-E4/Kc AC Three Phase 3p4w Digital Multifunction Programmable Smart Intelligent Electric RS485 Modbus RTU Energy Power Meter Kwh Meter for Switch Cabinet

Amc72L-E4/Kc AC Three Phase 3p4w Digital Multifunction Programmable Smart Intelligent Electric RS485 Modbus RTU Energy Power Meter Kwh Meter for Switch Cabinet

Package size per unit product 17.00cm * 15.00cm * 13.00cm Gross weight per unit product 0.580kg Product DescriptionAMC72
Basic Info
Model NO. AMC72L-E4/KC
Electric Equipment Three-phase Four-wire
Theory Electronic Meter
Power Meter Connection Terminal
Measured Signal Pulse Peak
Type Energy Meter
Certification RoHS, ISO, CE
Customized Customized
Product Name 3 Phase Multifunction Harmonic Energy Power Monito
Brand OEM ODM
Auxiliary Power Supply AC 220V
Reference Frequency 45~65Hz
Input Voltage 230/400V
Accuracy Class 1
Certificate Ce
Transport Package Fob Shanghai
Specification 96*96mm
Trademark ACREL
Origin China
HS Code 9028301400
Production Capacity 10000PCS/Per Month
Packaging & Delivery
Package size per unit product 17.00cm * 15.00cm * 13.00cm Gross weight per unit product 0.580kg
Product Description
AMC72L-E4/KC lcd intelligent power collection and monitoring energy meterGeneralDimensionTechnical Parameters
1. Function Overview
FunctionDescription&Value

Measurement

Three-phase AC kWh, kVarh, Active Power, Reactive Power, Forward&Reverse Power, Current, Voltage, Zero Sequence Voltage, Zero sequence Current, Voltage-phase Angle, Voltage&Current Unbalance, Power Factor,Harmonic, Frequency

Display

LCD display

Communication

(Optional)

RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity)
Baud Rate 1200~38400 bps etc.

Alarm Output

(Optional)

1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC,
Used for high,low,unbalance alarm etc.

Analog Output

(Optional)

1~5V DC or 4~20mA DC

DI/DO Switching

(Optional)

DI (Digital input): 2-channel or 4-channel dry contact digital input with built in power supply
DO (Digital output): 2-channel digital output with NO relay contact. Capacity: 3A/30V DC,3A/250V AC

2. Main Parameters
ParameterDescription&Value
InputRated VoltageAC Voltage Input: 400V AC L-L (via direct connetion); 100V AC L-L (via -/100V AC PTs)
Rated Current AC Current Input: 5A AC or 1A AC (via -/5A AC or -/1A AC CTs)
OverloadCurrent&Voltage input overload:1.2 times rated value(continuous); 10 times rated value /1 second
Frequency45~65Hz
Power ConsumptionPower consumption of each current&voltage input circuit is less than 0.5VA
Measuring AccuracyVoltage0.2%
Current0.2%
Active Power0.5%
Reactive Power1.0%
kWh0.5%
kVarh1.0%
Frequency±0.05Hz
Harmonic±1%
Power SupplyVoltage Range 85-265V AC/DC; 24V or 48V DC (±20%)
Power Consumption≤10VA
Insulation resistance≥ 100MΩ
Power frequency withstand voltageBetween Power supply//Switching Output// Current Input//voltage Input and Transmitting// Communication //Pulse Output//switching input AC 2 kV 1min;
Between Power supply,switching output,Current Input,voltage Input AC 2 kV 1min;
Between Transmitting,Communication,Pulse Output,switching input AC 1kV 1 min;

3. Environment
ConditionDescription&Value
TemperatureOperation: -25ºC~+65ºC; Storage: -40°C ~+80°C
Humidity≤95%RH,no condensation,without corrosive gas
Altitude≤ 2500m

 

Wiring
Wiring method of 3 phase 3 wireWiring method of 3 phase 4 wire

 

InstallationTypical connection